SKU: GS1000
Capacity 1000VA / 600W
Topology Offline (standby)
Waveform Simulated sine wave
Input voltage range 140–300 VAC
Transfer time 4–8 ms (13 ms max)
Battery 12V 7Ah lead-acid × 2
Backup time ≈ 20 min for a desktop PC
Output sockets 3 × universal + 250Vac/10A breaker
Protection Short circuit / overload / overcharge / overdischarge
AVR Boost & buck automatic regulation
Net weight ≈ 4 kg
Warranty 1 year

The GS1000 is an economical 1000VA / 600W offline (standby) tower UPS with AVR voltage regulation and 4–8 ms transfer — simple PC backup power for offices, POS counters and monitoring rooms.

Reliable 1000VA Offline UPS for PC and Office Equipment

The GS1000 offline UPS is ulinkeep’s economical standby tower unit for desktop PCs, cash registers, CCTV recorders and small network devices. When utility power fails, it transfers to battery in 4–8 ms and keeps equipment running long enough to save files and shut down safely — no lost orders, no corrupted data.

The black tower chassis keeps operation deliberately simple: one ON/OFF power button and one STATUS LED on the front panel, and quiet side ventilation with no fan noise above 40 dB. As an entry-level uninterruptible power supply, it offers a compact footprint and a friendly price — the most common PC backup power choice for SMB offices, retail counters and monitoring rooms.

GS1000 offline UPS compact tower design with side ventilation
GS1000 tower chassis — ready for OEM logo and panel customization
GS1000 offline UPS 1000VA compact tower, three-quarter angle view
Compact tower offline UPS, three-quarter view

Watch the 45-second demo: metal case, compact size, one-button start, automatic charging and short-circuit protection.

Front Panel: One Button, Clear Status at a Glance

Press the ON/OFF button to start or stop the UPS; the STATUS LED shows the power state instantly. In NORMAL state the LED lights steady green while mains supply is present. In BACKUP state the LED flashes orange with a beep every 10 seconds while the offline UPS runs on battery; when the battery runs low the buzzer beeps every second to warn you to save your work and shut down. On fault, the LED turns red and the buzzer sounds continuously.

GS1000 offline UPS front panel with ON/OFF power switch and STATUS LED
Front panel: ON/OFF switch and STATUS LED
GS1000 offline UPS front panel diagram: power switch and LED indicator, NORMAL and BACKUP states
LED indicator states: NORMAL and BACKUP

Rear Panel: Universal Sockets, Breaker and AC Input

Three universal output receptacles accept local plugs for PC hosts, monitors and POS terminals, protected by a 250Vac/10A circuit breaker; the AC input keeps charging the battery even when the UPS is switched off (off-mode charging). Protection covers short circuit, overload, overcharge and overdischarge. The unit is generator compatible and supports cold start, so the offline UPS can be powered up directly from battery without mains.

GS1000 offline UPS rear panel with universal output sockets, 250Vac/10A circuit breaker and AC input
Rear panel: 3 universal output sockets and 250Vac/10A breaker
GS1000 offline UPS rear panel diagram: circuit breaker, output sockets and input socket
Rear panel internals: breaker, output sockets, input socket

Application Scenarios for Offline UPS Backup

This offline UPS suits scenarios where short backup and stable voltage matter more than long runtime: SMB offices (front-desk PC, cash-drawer host, printer), chain-store POS counters (POS + scanner + receipt printer), monitoring and weak-current rooms (DVR/NVR, small switches), education and training labs, and small clinics or studios.

In regions with unstable grids, the boost/buck AVR regulates high or low mains first, so the battery is saved for real outages. If you need DC backup for routers and IP cameras instead, our B600T mini DC UPS covers 12V DC loads.

OEM/ODM Customization for Your Brand

Ulinkeep supports full OEM/ODM for this standby series (400VA–2000VA): logo silkscreen and panel customization, drawing-based and sample-based development, custom socket standards (EU/US/UK/universal), voltage output and packaging. Custom design proposals in 3 days, samples in 7 days, free replacement parts and online technical support during cooperation.

Packaging and logo/graphic customization start from 500 sets — a proven path for distributors, computer channel resellers and system integrators building their own brand on this offline UPS platform.

GS1000 offline UPS side view with ventilation grille
Ventilation design keeps the offline UPS cool and quiet (< 40 dB)
GS1000 offline UPS applications: PC computer, POS cash register, monitoring systems, small network switches
Applications: PC, POS, monitoring, small network switches

GS1000 Offline UPS Specifications

Backup power comes from two 12V 7Ah lead-acid batteries, giving roughly 20 minutes for a standard desktop PC, with a maximum charge current of 1.0 A. The specification sheet below is shared by the 400VA–2000VA standby series; the GS1000 is the 1000VA / 600W model.

Specification Value
Model GS1000
Capacity 1000VA / 600W
Topology Offline (standby)
Waveform (battery mode) Simulated sine wave
Input voltage range 140–300 VAC
Input frequency 50/60 Hz auto sensing
Output voltage (battery mode) 220/230/240 VAC ± 10%
Output frequency (battery mode) 50 Hz ± 1 Hz or 60 Hz ± 1 Hz
Transfer time Typical 4–8 ms, 13 ms max
Battery 12V 7Ah lead-acid × 2
Backup time ≈ 20 minutes for a desktop PC
Maximum charge current 1.0 A
Output sockets 3 × universal receptacles, 250Vac/10A breaker
Indicators AC mode: green / battery mode: orange flash / fault: red
Alarm Battery mode: every 10 s; low battery: every 1 s; overload: every 0.5 s; fault: continuous
Protection Short circuit, overload, overcharge, overdischarge
AVR Boost and buck automatic voltage regulation
Dimension (D×W×H) 345 × 123 × 189 mm
Net weight ≈ 4 kg
Operating environment 0–90% RH @ 0–40°C (non-condensing), noise < 40 dB
Warranty 1 year
Brand ulinkeep

Frequently Asked Questions

How many PCs can the GS1000 offline UPS support, and for how long?

Rated 1000VA/600W — it carries one standard desktop PC for about 20 minutes. For a PC plus monitor, calculate by actual load; it is designed for graceful shutdown, not extended work.

Does it work in regions with unstable voltage?

Yes. The input range is 140–300 VAC with boost/buck AVR: the offline UPS stabilizes high or low mains first and switches to battery only when power truly fails, saving battery life.

Will my computer reboot during the switch?

Transfer time is 4–8 ms typical (13 ms max) — short enough for normal PCs. For precision servers, choose a true online (double-conversion) UPS instead.

What waveform does it output, and what can it power?

A simulated (modified) sine wave, suitable for computers, monitors, POS terminals and CCTV recorders. Avoid motor-driven inductive loads and precision medical equipment.

How long does the battery last, and can I replace it myself?

The 12V 7Ah lead-acid batteries last 3–5 years. We recommend replacement by a qualified technician; overcharge, overdischarge, short-circuit and overload protection plus low-battery alarms are built in.

What is the MOQ and lead time for customization?

Packaging and logo customization start from 500 sets. Custom artwork in 3 days, samples in 7 days, 1-year warranty with free spare boards for quality issues.

Scroll to Top

How can we help you?

For any wholesale or custom questions, just reach out — we'll reply within 2 hours,Email: sales@ulinkeep.com, WhatsApp: 8619511387786